How Your Cooler Works

Understanding your walk in cooler will save you money and frustration. Many cooler repair in Illinois are caused by not understanding the operation of commercial refrigeration equipment. Your walk in refrigerator is very similar to a commercial reach-in refrigerator. It is not similar to a residential refrigerator. A household refrigerator is actually a freezer that uses some of the freezer’s air to cool the refrigerator part.

A walk in cooler moves heat from the box to the space around the condenser. Typical temperature ranges are from 35 degrees Fahrenheit to 41 degrees. Below 35 degrees a forced defrost cycle is needed to avoid freeze ups. This is how a walk in cooler works. This example will use a box that has a thermostat that is set at 40 degrees with a 5 degree differential.

The Thermostat Calls for Cooling

http://www.hometoys.com/htinews/apr03/articles/hvaczone/Typical%20System.jpg

The temperature has risen to the set point of 40 degrees. The thermostat closes and the compressor and condenser fan comes on. The condenser fan may cycle on and off in cold ambient temperatures.
The fans blow cold air out of the evaporator. The air circulates around the box absorbing heat. The warmed air is pulled into the back of the evaporator. The air is cooled as it passes through the evaporator.
The evaporator fan continues to run as the temperature drops to 35 degrees. There maybe slight ice build up on the evaporator. This is normal, since the coil in the evaporator is about 10 degrees colder than the 35 degree air entering it.

The Thermostat is Satisfied

When the temperature reaches 35 degrees (40 degree set point minus 5 degree differential), the thermostat cuts the compressor and the condenser fan motor off. The evaporator fans continue to run. The fans in the walk in cooler should always be running.
Heat is absorbed through the walls, from door openings and from the product. The temperature continues to rise. Any frost that was built up on the evaporator will melt now. This is called off cycle defrost. The air needs to be at least 35 degrees for dependable defrost.
This is an important point. If the walk-in cooler can not reach the set point temperature, the compressor will not cut off and evaporator can not defrost. This can be caused by the thermostat being set too low. Liquid refrigerant can make it back to the compressor and cause compressor failure.
The air in the box continues to warm until it reaches 40 degrees. Then the thermostat calls for cooling again. A walk-in freezer works in the same way plus it has a forced defrost cycle.

Want to learn more about your cooler? Have a cooler repair problem? If you answered yes to these questions, then it is high time to consider a freezer repair technician. If you need assistance in cooler repair in Illinois, Northeast Cooling has specialized in Commercial Refrigeration and Ice Machine sales, service and repair for more than 15 years. Cooler, Freezer, and Ice Machine repairs done right the first time. Count on Northeast Cooling for Quality Refrigeration Repairs.

3 comments:

  1. Thanks for sharing your information on commercial refrigeration....so much emphasis is given on how the cooler works....... Looking for commercial refrigerator manufacturers i would like to suggest to visit this site http://www.marcrefrigeration.com/

    ReplyDelete
  2. just linked this article on my facebook account. it’s a very interesting article for all.

    Commercial Refrigeration

    ReplyDelete
  3. Hey There. I found your blog using msn. This is a very well written article. I’ll be sure to bookmark it and come back to read more of your useful info. Thanks for the post. I’ll definitely return. Sub-Zero, Viking, U-Line ICE FREEZER REPAIR IN CHINO

    ReplyDelete